| Category | Specification |
|---|---|
| Industry | Water Treatment & Filtration |
| Frameworks | IEC 62443, MITRE ATT&CK for ICS, ISA-95 Purdue Model |
| Environment | 5-Zone Segmented Docker Lab with L3/L4 Firewall |
| Monitoring | Protocol-Aware (Modbus/TCP) Anomaly detection |
| Evidence | Verified Attack Simulation Logs |
This repository contains a full-scale, simulated industrial environment designed to demonstrate the implementation of robust security controls within an Operational Technology (OT) context. The project encompasses the entire lifecycle of an IT/OT Security Engineer's responsibilities: from architectural design and network segmentation based on the Purdue Model, to threat modeling, detection engineering, and IEC 62443 compliance mapping.
The lab simulates a Water Treatment & Filtration Facility, facilitating a hands-on platform for validating security configurations and detection rules against realistic ICS attack vectors.
The environment is segmented into logical levels according to the ISA-95 Purdue Model, ensuring strict isolation of critical control processes.
graph TD
%% Level Definition
subgraph L4_5 ["Level 4 & 5: Enterprise"]
A[Attacker Simulation]
B[Corporate Workstation]
end
subgraph DMZ ["Industrial DMZ"]
JH[Jump Host / Bastion]
RP[Reverse Proxy]
end
subgraph L3 ["Level 3: Operations"]
C[Historian - InfluxDB]
D[Engineering Workstation]
end
subgraph L2 ["Level 2: Supervisory"]
E[SCADA / HMI Server]
end
subgraph L1 ["Level 1: Control"]
F1[PLC-01: Intake]
F2[PLC-02: Treatment]
F3[PLC-03: Distribution]
end
subgraph L0 ["Level 0: Field Devices"]
G[Sensors/Actuators]
end
%% Conduits
B ---|VPN/HTTPS| JH
JH ---|RDP/SSH| D
D ---|S7/Modbus| F1
E ---|Modbus/TCP| F1
E ---|Modbus/TCP| F2
E ---|Modbus/TCP| F3
F1 ---|Process Flow| F2
F2 ---|Process Flow| F3
F3 ---|Hardwired| G
%% Styling
style DMZ fill:#fff2cc,stroke:#d6b656,stroke-width:2px
style L1 fill:#fdb,stroke:#333,stroke-width:2px
- Level 4/5 (Enterprise): Corporate LAN, Attacker Simulation, External Monitoring.
- Industrial DMZ: Broker for remote access (Jump Host) and data visualization (Proxy).
- Level 3 (Operations): Historian (InfluxDB) and the segregated Engineering Workstation (EWS).
- Level 2 (Supervisory): Centralized SCADA/HMI (Scada-LTS) for plant-wide visibility.
- Level 1 (Control): Distributed Control via three PLCs (Intake, Treatment, Distribution).
- Level 0 (Field): Physical process assets (Valves, Pumps, Flow Meters).
- Architecture & Design
- Lab Environment
- Asset Inventory
- Threat Model & Risk Analysis
- Detection & Monitoring
* [Modbus Anomaly Detection](./detection/rules/modbus_anomaly.py)
* [**Physics-Aware Safety Monitor**](./detection/rules/process_safety_violation.py)
* [Cross-Zone Traffic Alerter](./detection/rules/cross_zone_traffic.py)
* [Brute Force Detection](./detection/rules/ot_brute_force.py)
* [**Live Detection Evidence (JSON Logs)**](./detection/logs/alerts.json)
To bridge the gap between technical implementation and industrial standards (Exceltic/ISA-62443 requirements), this lab includes formal documentation:
- Asset Inventory (LDR Style): A complete map of the lab's hardware and network footprints.
- Incident Response Playbook: "Safety-First" response procedures for industrial security events.
- Hardening Guide (STIG): Mandatory security baselines for both Gateway and PLCs.
- Verification Test Plan: Formal mapping of simulations to security requirements (V&V).
This lab currently utilizes Modbus TCP as a representative industrial protocol. In a production rollout (e.g., Railway/Transportation):
- Protocols: The detection logic would be expanded to support PROFINET, Ethernet/IP, and OPC-UA using modular dissectors.
- Asset Discovery: Manual inventory would be replaced by continuous passive monitoring (e.g., Zeek/Nozomi) linked to the
asset_inventory.csv. - Scale: The architecture is designed to handle thousands of tags across hundreds of distributed PLCs.
- Tiered Data Architecture (ADR-02): By isolating the Historian in Level 3 (Operations) rather than Level 2 (Supervisory), we create a unidirectional data flow that prevents corporate IT users from ever reaching the control network directly. This fulfills the IEC 62443 requirement for restricted data access between functional zones.
- Chokepoint Enforcement (ADR-05): Utilizing a dedicated Linux gateway running
iptablesinstead of standard Docker bridge networking allows for granular L3/L4 traffic control. This architecture ensures that every inter-zone conduit is explicitly authorized, mirroring the functionality of industrial-grade firewalls. - Availability-First Detection: Our custom detection rules prioritize high-signal industrial anomalies (e.g., Modbus writes from unauthorized IPs) over generic signature matching. This approach minimizes false positives, ensuring that security monitoring does not interfere with the availability of critical industrial processes.
To spin up the entire simulated environment (OpenPLC, HMI, Historian, and Firewall):
# Clone the repository
git clone https://github.com/yourusername/ot-security-lab.git
cd ot-security-lab/lab-environment
# Start the environment
sudo docker compose up -d
# Apply firewall rules
sudo docker cp network-config/firewall-rules.sh ot_gateway:/firewall-rules.sh
sudo docker exec ot_gateway /firewall-rules.sh- Virtualization: Docker, Docker Compose V2
- Industrial: OpenPLC Runtime (v4), Scada-LTS (HMI), InfluxDB 1.8 (Historian)
- Security Infrastructure:
iptables(Zone Firewall), Scapy (Custom IDS),iputils-ping,nmap - Frameworks: IEC 62443-3-2 (Zones/Conduits), MITRE ATT&CK for ICS, ISA-95 Purdue Model
- Monitoring: Centralized JSON logging (
alerts.json)
- Logical vs. Physical Data Diode: Unidirectional flow is enforced via
iptables. High-consequence sites require hardware-based optical data diodes. - Protocol Scope: Currently limited to Modbus/TCP.
- Simulation vs. Emulation: PLCs are software-simulated (OpenPLC) rather than hardware-emulated.
- SIEM Integration: Centralized logs using Grafana, Loki, and Promtail.
- Adversary Emulation: Developing playbooks for Industroyer and TRITON-style attack simulations.
- IEC 62443-3-2: Zones and Conduits implemented.
- MITRE ATT&CK for ICS: Tactics T0800–T0890 mapped in threat model.