Vitosoft uses a large Microsoft SQL Server database ecnViessmann.mdf/ldf to keep track of all heating systems, devices and all their parameters. Besides that database, the information is also available as XML files, which is what we will use to find out all events, which are supported by our system.
- Device is a vendor. Only one exists: Viessmann
- Datapoints are heating units or devices. Typically there is only one active at any given time. There are about 400 datapoints known.
- Events are readable and/or writeable values or callable functions to the heating unit.
- Event Values are specific values for specific events. This allows naming certain values or creating named enums.
- Event Groups allow grouping of events, e.g. all solar parameters in one group. This is only used for a nicer presentation within the Vitosoft application.
- Display Condition and Display Condition Group are used to hide individual events, e.g. if not solar system is installed, then it will not show up in the UI. It allows relatively complex terms.
There are several XML files of interest. Warning: You actually need to launch Vitosoft once for it to generate the ecnDataPointType.xml and ecnEventType.xml files from ecnViessmann.mdf. The outdated files from the EXE will be moved to a folder named configbackup.
DPDefinitions.xml- a massive almost 200MB large file, which contains the database of all data points in XML formatecnVersion.xml– contains theDataPointDefinitionVersion. It is regenerated on first launch from the SQL database, which bumps the version number to0.0.26.4683.ecnDataPointType.xml- The file contains all information needed to identify the Viessmann heating unit. TheIDof the unit is used asAddressin theecnDatapointTypeinsideDPDefinitions.xml.ecnEventType.xml- Events are readable and/or writeable values or callable functions to the heating unit. TheIDof the event is used asAddressin theecnEventTypeinsideDPDefinitions.xml.ecnEventTypeGroup.xml- this XML allows to combines events into groups, like all solar events together. TheIDof the event is used asAddressin theecnEventTypeGroupinsideDPDefinitions.xml.Textresource_de.xml(for German) andTextresource_en.xml(for English) - translateLabelsinto aValue, which is a readable label for a field in the databases if theNamestarts with@@.sysDeviceIdent.xml- additional common events, which are needed to identify a specific heating system.
Eight addresses to be used via Virtual Read are defined for all devices.
| Viessmann internal name | Address | in XML files |
|---|---|---|
ProtocolIdentifierOffset |
0xF0 |
ecnsysDeviceIdentF0 |
GRUPPENIDENTIFIKATION |
0xF8 |
sysDeviceGroupIdent |
REGLERIDENTIFIKATION |
0xF9 |
sysDeviceIdent |
HARDWAREINDEX |
0xFA |
sysHardwareIndexIdent |
SOFTWAREINDEX |
0xFB |
sysSoftwareIndexIdent |
VERSION_LDA |
0xFC |
sysProtokollversionLDAIdent |
VERSION_RDA |
0xFD |
sysProtokollversionRDAIdent |
VERSION_SW1 |
0xFE |
sysHighByteDeveloperVersionIdent |
VERSION_SW2 |
0xFF |
sysLowByteDeveloperVersionIdent |
ecnDataPointType.xml contains all information to identify supported systems. It is essential to run Vitosoft once for this file to be generated correctly – otherwise you have a very outdated version.
IDis the global id, which is referenced by other databases asAddress.Descriptionis an internal description of the systemIdentificationmust matchsysDeviceGroupIdentandsysDeviceIdent, which are combined as 4-digit hex-values. This is the main way to identify the actual system.IdentificationExtensionallows to identify specific hardware and software revisions, which might have different limitations. It must match the combined hex-values ofsysHardwareIndexIdentandsysSoftwareIndexIdent. If this key is larger than 4 hex-characters, it does not seem to match with the Vitosoft app, it might be used for an internal app only.IdentificationExtensionTillif this one exists, thenIdentificationExtensiontillIdentificationExtensionTillis a range of systems, which match.EventOptimisationcan be 0 (allowed) or 1 (not allowed). It allows Vitosoft to combine certain read requests into one for better performance.EventOptimisationExceptionListdisables event optimization for specific events.Optionsadditional options for the system. Onlyundefined,trendingandappointeddateare defined and i think none of them is used by Vitosoft.ControllerTypecan have the following values:GWG= 0,WP= 1,NR= 2,VC300Old= 3,BHKW= 4,WO1A= 5,VC100Old= 6,VC200Old= 7,VC100New= 8,VC200New= 9,VC300New= 10,WPR3= 11,VitotwinGW_BATI= 12,NRP= 14 – it seems that only VC100–VC300 are supported by Vitosoft Optolink.ErrorTypecan have the following values: 0 = Unknown, 1 = Default, 2 = VCom, 3 = WP, 4 = BHKW, 5 = DefaultRPC, 6 = WPR3, 7 = VitotwinGW_BATI. It seems to be ignored by Vitosoft.F0match theProtocolIdentifierOffsetvalue.F0Tillsimilar toIdentificationExtensionTill, it allows defining a range.
There are some special cases for identification of systems, which are hard-coded in the Vitosoft application, be aware.
ecnConverter → ecnDeviceType (Vendor, always Viessmann) → ecnDatapointType (Heating units, devices) → ecnEventType (parameter) → ecnEventValueType (individual values for a specific parameter)
ecnEventTypeGroup (groups of parameters) → ecnEventType (individual parameter)
Base class, only exist once. Can be ignored.
Id unique ID of the converters
<Id>1</Id>
<ConverterClassName>vsm.Dispatcher.Notification</ConverterClassName>
<ConverterAssembly>vsm.Dispatcher, Version=1.2.0.0, Culture=neutral, PublicKeyToken=6ffa2c8f99f9eb6d</ConverterAssembly>
Defines a relationship between the converter and the devices. There is only one devices: Viessmann. Can be ignored.
ConverterId is a reference to Id in ecnConverter
DeviceTypeTechnicalIdentificationAddress is a reference to TechnicalIdentificationAddress in ecnDeviceType
<ConverterId>1</ConverterId>
<DeviceTypeTechnicalIdentificationAddress>7</DeviceTypeTechnicalIdentificationAddress>
Sits below the converter, only exists once (ID 54). Unimportant when communicating with the unit. The "device" is always Viessmann! Can be ignored.
Id unique ID of the device
Name name of the device
Manufacturer manufacturer of the device
Description internal description
StatusEventTypeId ecnEventType with the status
TechnicalIdentificationAddress a reference to ecnConverterDeviceTypeLink
<Id>54</Id>
<Name>Viessmann Anlage</Name>
<Manufacturer></Manufacturer>
<Description></Description>
<StatusDataPointTypeId>1</StatusDataPointTypeId>
<TechnicalIdentificationAddress>7</TechnicalIdentificationAddress>
Defines a relationship between a device and multiple data points. A device in this context is "Viessmann", while data points are the heating units. Can be ignored.
DeviceTypeId is a reference to Id in ecnDeviceType
DataPointTypeId is a reference to Id in ecnDatapointType
<DeviceTypeId>54</DeviceTypeId>
<DataPointTypeId>1</DataPointTypeId>
A data point is an actual heating unit. There are about 400 defined. This is the first important type!
Id unique ID of the data point
Name name of the data point. '@@' as a prefix points into Textresource_xx.xml for translation.
Description internal info about this datapoint. Always in German.
StatusEventTypeId a ecnEventType with the status
Address a reference to the ID in ecnDataPointType.xml, which describes how the heating unit can be identified.
<Id>350</Id>
<Name>@@viessmann.datapointtype.name.VScotHO1_72</Name>
<Description>Technische Produktbeschreibung: ab Softwareindex 72 (Projekt Neptun)</Description>
<StatusEventTypeId>1</StatusEventTypeId>
<Address>VScotHO1_72</Address>
Defines a relationship between a data point and multiple events.
DataPointTypeId is a reference to Id in ecnDatapointType
EventTypeId is a reference to Id in ecnEventType
<DataPointTypeId>10</DataPointTypeId>
<EventTypeId>2</EventTypeId>
Events are individual parameter in the heating unit.
Id unique ID of the event
EnumType Is this event an enum value? Only true or false are valid.
Name name of the events. '@@' as a prefix points into Textresource_xx.xml for translation.
Address a reference to the ID in ecnEventType.xml, which has information on how to access the value in the heating unit as well as value ranges or lists (for enums)
Conversion How to convert the binary value, see conversion
Description internal info about this event. Always in German.
Priority The default is 100, sometimes (enums, adressen 0xF8…0xFF=1…8) it is 50. Probably used to sort the order of requests.
Filtercriterion always seems to be true?
Reportingcriterion always seems to be true?
Type allowed access to this event: 1=Read-only, 2=Read/Write, 3=Write-only
URL Vitosoft internal web server URL to visualize the datapoint, e.g. an editor the time/date scheduling.
DefaultValue default value for this event, if not read from the heating unit. Can be an integer or float.
<Id>329</Id>
<EnumType>false</EnumType>
<Name>@@viessmann.eventtype.name.GWG_Aussentemperatur</Name>
<Address>GWG_Aussentemperatur~0x006F</Address>
<Conversion>Div2</Conversion>
<Description>@@viessmann.eventtype.GWG_Aussentemperatur.description</Description>
<Priority>100</Priority>
<Filtercriterion>true</Filtercriterion>
<Reportingcriterion>true</Reportingcriterion>
<Type>1</Type>
<URL></URL>
<DefaultValue></DefaultValue>
Defines a relationship between an event and multiple event values.
EventTypeId is a reference to Id in ecnEventType
EventValueId is a reference to Id in ecnEventValueType
<EventTypeId>1</EventTypeId>
<EventValueId>13287</EventValueId>
Value of an event, used to define conditions.
Id unique ID of the event value
Name name of this event value. '@@' as a prefix points into Textresource_xx.xml for translation.
<Id>2</Id>
<Name>@@viessmann.eventvaluetype.name.Absenkzeit_gelerntA1M1</Name>
<EnumReplaceValue></EnumReplaceValue>
<StatusTypeId>0</StatusTypeId>
<Unit>ecnUnit.Minuten</Unit>
<DataType>Int</DataType>
<Stepping>10</Stepping>
<LowerBorder>0</LowerBorder>
<UpperBorder>250</UpperBorder>
<Description></Description>
Allows to group events together, like all solar events. Used for a more pleasant visualization.
Id unique ID of the group
Name name of the group. '@@' as a prefix points into Textresource_xx.xml for translation.
ParentId is a reference to Id in ecnEventTypeGroup. -1 = no parent.
EntrancePoint is the group an entrance or only a subgroup of another one? Only true or false are valid.
Address a reference to ecnEventTypeGroup.xml
DeviceTypeId is a reference to Id in ecnDeviceType. There is only one: 54 (Viessmann)
DataPointTypeId is a reference to Id in ecnDatapointType.
OrderIndex Sorting order for the group within the DeviceTypeId/DataPointTypeId selection.
<Id>3</Id>
<Name>@@viessmann.eventtypegroup.name.Dekamatik_E~10_Bedienung</Name>
<Description></Description>
<ParentId>-1</ParentId>
<EntrancePoint>true</EntrancePoint>
<Address>Dekamatik_E~10_Bedienung</Address>
<DeviceTypeId>54</DeviceTypeId>
<DataPointTypeId>144</DataPointTypeId>
<OrderIndex>1</OrderIndex>
Defines a relationship between a group and multiple events including an order value.
EventTypeId is a reference to Id in ecnEventType
EventTypeGroupId is a reference to Id in ecnEventTypeGroup
EventTypeOrder ist die Sortierreihenfolge des Event Type innerhalb der Gruppe. Dubletten sind möglich!
<EventTypeId>1134</EventTypeId>
<EventTypeGroupId>4</EventTypeGroupId>
<EventTypeOrder>17</EventTypeOrder>
A single condition to hide an event in the UI, because e.g. the hardware does not exist or other settings prohibit this event. As you can see: it allows to compare the event with a specific value for this event. This is extremely common for events, which are enums. But it is also possible to compare the event with a specific value, which could be a temperature limit.
Id unique ID of the display condition
Name name of the display condition - never set
ConditionGroupId is a reference to Id in ecnDisplayConditionGroup
EventTypeIdCondition is a reference to Id in ecnEventType
EventTypeValueCondition is a reference to Id in ecnEventValueType
Description internal info for this display condition
Condition compare operator: 0=Equal, 1=NotEqual, 2=GreaterThan, 3=GreaterThanOrEqualTo, 4=LessThan, 5=LessThanOrEqualTo
ConditionValue defined, if Condition >= 2, contains the value for the comparism
<Id>19922</Id>
<Name></Name>
<ConditionGroupId>5993</ConditionGroupId>
<EventTypeIdCondition>5276</EventTypeIdCondition>
<EventTypeValueCondition>8403</EventTypeValueCondition>
<Description></Description>
<Condition>2</Condition>
<ConditionValue>300</ConditionValue>
A display condition group allows combining multiple display conditions via AND or OR to a complex term. Best to look at the Python sample code for more details.
Id unique ID of the condition group
Name name of the condition group
Type 1=AND or 2=OR all conditions
ParentId is a reference to Id in ecnDisplayConditionGroup. -1 = no parent.
Description internal info for this condition group
EventTypeIdDest is a reference to Id in ecnEventType. -1 = not defined
EventTypeGroupIdDest is a reference to Id in ecnEventTypeGroup. -1 = not defined
<Id>1</Id>
<Name>VDensHC2 Überblick Solar</Name>
<Type>1</Type>
<ParentId>-1</ParentId>
<Description></Description>
<EventTypeIdDest>-1</EventTypeIdDest>
<EventTypeGroupIdDest>5604</EventTypeGroupIdDest>
If a ConversionFactor is not defined, it is assumed to be 1. If a ConversionOffset is not defined, it is assumed to be 0.
| conversion name | result type | conversion of the byte buffer buf |
|---|---|---|
| NoConversion | – | no conversion |
| MultOffset | Double | V * ConversionFactor + ConversionOffset |
| Mult2 | Double | V * 2 |
| Mult5 | Double | V * 5 |
| Mult10 | Double | V * 10 |
| Mult100 | Double | V * 100 |
| Div2 | Double | V / 2 |
| Div10 | Double | V / 10 |
| Div100 | Double | V / 100 |
| Div1000 | Double | V / 1000 |
| Time53 | String | HH:MM with HH=buf[0] >> 3; MM=(buf[0] & 7) * 10; or an empty string, if buffer[0]==0xFF |
| DateBCD | DateTime | BCD in buf with 8 bytes YYYYMMDDxxHHMMSS |
| DateTimeBCD | DateTime | identical to DateTimeBCD |
| DateTimeVitocom | ? | NOT IMPLEMENTED |
| Sec2Minute | Double | Round(V / 60, 2) |
| Sec2Hour | Double | Round(V / (60*60)), 2) |
| Sec2Day | Double | Round(V / (24*60*60), 2) |
| Sec2Week | Double | Round(V / (7*24*60*60), 2) |
| Sec2Month | Double | NOT IMPLEMENTED |
| Estrich | ? | NOT IMPLEMENTED |
| Kesselfolge | ? | NOT IMPLEMENTED |
| IPAddress | String | IP4 buf[3]+'.'+buf[2]+'.'+buf[1]+'.'+buf[0] |
| Steuerzeichen | ? | NOT IMPLEMENTED |
| UTCDiff2Hour | ? | NOT IMPLEMENTED |
| UTCDiff2Day | ? | NOT IMPLEMENTED |
| UTCDiff2Month | ? | NOT IMPLEMENTED |
| HourDiffSec2Hour | ? | NOT IMPLEMENTED |
| VitocomEingang | ? | NOT IMPLEMENTED |
| Vitocom300SGEinrichtenKanalLON | ? | NOT IMPLEMENTED |
| Vitocom300SGEinrichtenKanalMBUS | ? | NOT IMPLEMENTED |
| Vitocom300SGEinrichtenKanalWILO | ? | NOT IMPLEMENTED |
| VitocomNV | ? | NOT IMPLEMENTED |
| Vitocom3NV | ? | NOT IMPLEMENTED |
| HexByte2DecimalByte | ByteArray | standard byte array |
| RotateBytes | ByteArray | reverse all bytes in the array |
| Phone2BCD | ByteArray | converts BCD data (0-9) in a ByteArray. Assumes the BCD value 15 to be ignored. |
| ImpulszaehlerV300FA2 | ? | NOT IMPLEMENTED |
| DatenpunktADDR | ? | NOT IMPLEMENTED |
| DateTimeMBus | ? | NOT IMPLEMENTED |
| DateMBus | ? | NOT IMPLEMENTED |
| MultOffsetBCD | Double | Up to 0-4 byte LSB value V, then applies V * ConversionFactor + ConversionOffset |
| HexToFloat | ? | NOT IMPLEMENTED |
| MultOffsetFloat | Double | NOT IMPLEMENTED |
| HexByte2AsciiByte | ByteArray | standard byte array – same as HexByte2DecimalByte |
| DayToDate | DateTime | buf of up to 8 bytes will be interpreted as a 64-bit LSB value, which represents the number of days starting 1.1.1970 – UNIX timestamp |
| FixedStringTerminalZeroes | zero terminated string | |
| LastBurnerCheck | ? | NOT IMPLEMENTED |
| LastCheckInterval | ? | NOT IMPLEMENTED |
| Convert4BytesToFloat | Converts 4 IEEE bytes into a float |
Id unique ID of the config set
<Id>1</Id>
<Name>IO_VC_DE1</Name>
<ProcessingBL>vsmCommInterface.businesslogic.IOConfigSetProcessorBL, vsmCommInterface</ProcessingBL>
Id unique ID of the config set parameter
<Id>1</Id>
<ConfigSetId>1</ConfigSetId>
<Parameter>Evaluate</Parameter>
<Required>true</Required>
Used for translations of the interface in different languages. Not necessary to communicate with the system.
Id unique ID of the culture
Name ISO-Sprachcode
<Id>2</Id>
<Name>en</Name>
Error status (ecnEventType #1). The following Id are defined:
0 : Undefined (SortOrder = 100, ShowInEventTray = false)
1 : OK (SortOrder = 3, ShowInEventTray = false)
2 : Warning (SortOrder = 2, ShowInEventTray = true)
3 : Error (SortOrder = 1, ShowInEventTray = true)
4 : illegal value (SortOrder = 4, ShowInEventTray = true)
5 : --- (SortOrder = 5, ShowInEventTray = true)
Id unique ID of the status (0-5 are possible)
Name name of the status. '@@' as a prefix points into Textresource_xx.xml for translation.
ShowInEventTray Is the status value shown in the event tray?
Image Base64 of a GIF representing the status
SortOrder sort oder for the status
<Id>5</Id>
<Name>@@viessmann.vitodata.valuestatus.notevaluate</Name>
<ShowInEventTray>true</ShowInEventTray>
<Image>………</Image>