Skip to content

simulation is not running with an idf produced with generate_geometry_from_yaml #125

Description

@alexandrecuer
Program Version,EnergyPlus, Version 24.1.0-9d7789a3ac, YMD=2026.06.06 18:45,
   ************* Beginning Zone Sizing Calculations
   ** Warning ** Site:GroundTemperature:BuildingSurface: Some values fall outside the range of 15-25C.
   **   ~~~   ** These values may be inappropriate.  Please consult the Input Output Reference for more details.
   ** Warning ** ProcessScheduleInput: Schedule:Compact="HEATING_SCHEDULE" has missing day types in Through=12/31
   **   ~~~   ** Last "For" field=FOR:SUMMERDESIGNDAY
   **   ~~~   ** Missing day types="Holiday","CustomDay1","CustomDay2"
   **   ~~~   ** Missing day types will have 0.0 as Schedule Values
   ** Warning ** ProcessScheduleInput: Schedule:Compact="CONTROL_TYPE_SCHEDULE" has missing day types in Through=12/31
   **   ~~~   ** Last "For" field=FOR:SUMMERDESIGNDAY
   **   ~~~   ** Missing day types="Holiday","CustomDay1","CustomDay2"
   **   ~~~   ** Missing day types will have 0.0 as Schedule Values
   ** Warning ** GetSurfaceData: Construction WALL_OSB of interzone surface RDC_WALL3 does not have the same materials in the reverse order as the construction WALL_OSB of adjacent surface MEETING..FACE1
   **   ~~~   ** or the properties of the reversed layers are not correct due to differing layer front and back side values
   **   ~~~   ** ...but Nominal U values are similar, diff=[0.0000] ... simulation proceeds.
   **   ~~~   ** ...if the two zones are expected to have significantly different temperatures, the proper "reverse" construction should be created.
   **   ~~~   ** ...this problem for this pair will not be reported again.
   ** Warning ** CalcSurfaceCentroid: 2 Surfaces have the Z coordinate < 0.
   **   ~~~   ** ...in any calculations, Wind Speed will be 0.0 for these surfaces.
   **   ~~~   ** ...in any calculations, Outside temperatures will be the outside temperature + 9.750E-003 for these surfaces.
   **   ~~~   ** ...that is, these surfaces will have conditions as though at ground level.
   ** Warning ** CheckUsedConstructions: There are 12 nominally unused constructions in input.
   **   ~~~   ** For explicit details on each unused construction, use Output:Diagnostics,DisplayExtraWarnings;
   ** Warning ** DetermineShadowingCombinations: There are 1 surfaces which are receiving surfaces and are non-convex.
   **   ~~~   ** ...Shadowing values may be inaccurate. Check .shd report file for more surface shading details
   **   ~~~   ** ...Add Output:Diagnostics,DisplayExtraWarnings; to see individual warnings for each surface.
   ** Severe  ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RDC BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
   **   ~~~   ** ...the minimum that must be entered=[1].
   ** Warning ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RDC BASEBOARD", Summed radiant fractions for people + surface groups < 1.0
   **   ~~~   ** The rest of the radiant energy delivered by the baseboard heater will be lost
   ** Severe  ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
   **   ~~~   ** ...the minimum that must be entered=[1].
   ** Warning ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", Summed radiant fractions for people + surface groups < 1.0
   **   ~~~   ** The rest of the radiant energy delivered by the baseboard heater will be lost
   **  Fatal  ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:WaterErrors found getting input. Program terminates.
   ...Summary of Errors that led to program termination:
   ..... Reference severe error count=2
   ..... Last severe error=GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
   ************* Warning:  Node connection errors not checked - most system input has not been read (see previous warning).
   ************* Fatal error -- final processing.  Program exited before simulations began.  See previous error messages.
   *************
   ************* ===== Final Error Summary =====
   ************* The following error categories occurred.  Consider correcting or noting.
   ************* Nominally Unused Constructions
   ************* ..The nominally unused constructions warning is provided to alert you to potential conditions that can cause
   ************* ..extra time during simulation. Each construction is calculated by the algorithm indicated in the HeatBalanceAlgorithm
   ************* ..object. You may remove the constructions indicated (when you use the DisplayExtraWarnings option).
   *************
   ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Sizing Error Summary. During Sizing: 8 Warning; 2 Severe Errors.
   ************* EnergyPlus Terminated--Fatal Error Detected. 9 Warning; 2 Severe Errors; Elapsed Time=00hr 00min  0.75sec