Program Version,EnergyPlus, Version 24.1.0-9d7789a3ac, YMD=2026.06.06 18:45,
************* Beginning Zone Sizing Calculations
** Warning ** Site:GroundTemperature:BuildingSurface: Some values fall outside the range of 15-25C.
** ~~~ ** These values may be inappropriate. Please consult the Input Output Reference for more details.
** Warning ** ProcessScheduleInput: Schedule:Compact="HEATING_SCHEDULE" has missing day types in Through=12/31
** ~~~ ** Last "For" field=FOR:SUMMERDESIGNDAY
** ~~~ ** Missing day types="Holiday","CustomDay1","CustomDay2"
** ~~~ ** Missing day types will have 0.0 as Schedule Values
** Warning ** ProcessScheduleInput: Schedule:Compact="CONTROL_TYPE_SCHEDULE" has missing day types in Through=12/31
** ~~~ ** Last "For" field=FOR:SUMMERDESIGNDAY
** ~~~ ** Missing day types="Holiday","CustomDay1","CustomDay2"
** ~~~ ** Missing day types will have 0.0 as Schedule Values
** Warning ** GetSurfaceData: Construction WALL_OSB of interzone surface RDC_WALL3 does not have the same materials in the reverse order as the construction WALL_OSB of adjacent surface MEETING..FACE1
** ~~~ ** or the properties of the reversed layers are not correct due to differing layer front and back side values
** ~~~ ** ...but Nominal U values are similar, diff=[0.0000] ... simulation proceeds.
** ~~~ ** ...if the two zones are expected to have significantly different temperatures, the proper "reverse" construction should be created.
** ~~~ ** ...this problem for this pair will not be reported again.
** Warning ** CalcSurfaceCentroid: 2 Surfaces have the Z coordinate < 0.
** ~~~ ** ...in any calculations, Wind Speed will be 0.0 for these surfaces.
** ~~~ ** ...in any calculations, Outside temperatures will be the outside temperature + 9.750E-003 for these surfaces.
** ~~~ ** ...that is, these surfaces will have conditions as though at ground level.
** Warning ** CheckUsedConstructions: There are 12 nominally unused constructions in input.
** ~~~ ** For explicit details on each unused construction, use Output:Diagnostics,DisplayExtraWarnings;
** Warning ** DetermineShadowingCombinations: There are 1 surfaces which are receiving surfaces and are non-convex.
** ~~~ ** ...Shadowing values may be inaccurate. Check .shd report file for more surface shading details
** ~~~ ** ...Add Output:Diagnostics,DisplayExtraWarnings; to see individual warnings for each surface.
** Severe ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RDC BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
** ~~~ ** ...the minimum that must be entered=[1].
** Warning ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RDC BASEBOARD", Summed radiant fractions for people + surface groups < 1.0
** ~~~ ** The rest of the radiant energy delivered by the baseboard heater will be lost
** Severe ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
** ~~~ ** ...the minimum that must be entered=[1].
** Warning ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", Summed radiant fractions for people + surface groups < 1.0
** ~~~ ** The rest of the radiant energy delivered by the baseboard heater will be lost
** Fatal ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:WaterErrors found getting input. Program terminates.
...Summary of Errors that led to program termination:
..... Reference severe error count=2
..... Last severe error=GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
************* Warning: Node connection errors not checked - most system input has not been read (see previous warning).
************* Fatal error -- final processing. Program exited before simulations began. See previous error messages.
*************
************* ===== Final Error Summary =====
************* The following error categories occurred. Consider correcting or noting.
************* Nominally Unused Constructions
************* ..The nominally unused constructions warning is provided to alert you to potential conditions that can cause
************* ..extra time during simulation. Each construction is calculated by the algorithm indicated in the HeatBalanceAlgorithm
************* ..object. You may remove the constructions indicated (when you use the DisplayExtraWarnings option).
*************
************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
************* EnergyPlus Sizing Error Summary. During Sizing: 8 Warning; 2 Severe Errors.
************* EnergyPlus Terminated--Fatal Error Detected. 9 Warning; 2 Severe Errors; Elapsed Time=00hr 00min 0.75sec